SAMPA/SAMPA DAQ Registers

From ift
Revision as of 14:45, 3 November 2014 by Ave082 (talk | contribs) (Created page with "= SAMPA DAQ Registers = == Command and Control module registers == The registers for the command and control module, located at address 0x0000 from the UART or 0xFF200000 fro...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

SAMPA DAQ Registers

Command and Control module registers

The registers for the command and control module, located at address 0x0000 from the UART or 0xFF200000 from the HPS, is listed in table 4.1

Register name Address Type Default Description
SC_ADD [15:0] 0x00 RW 0x00 [4:0] Slow control: Register address
RW 0x00 [9:5] Slow control: Channel address
RW 0x00 [13:10] Slow control: Chip address
RW 0x00 [14] Slow control: Broadcast
RW 0x00 [15] Slow control: Write/ not read
SC_DAT [19:0] 0x01 RW 0x00 [19:0] Slow control: Data to write
SC_MASK [19:0] 0x02 RW 0x00 [19:0] Slow control: Mask for writing *
CMD [31:0] 0x03 RW 0x00 [15:0] Commands, see table 4.2
RW 0x00 [31:15] Loop count for commands
SC_RLT [19:0] 0x04 R 0x00 [12:0] Slow control: Response from SAMPA
SC_ERR [1:0] 0x05 R 0x00 [0] Error: Timeout waiting for response from slow control
R 0x00 [1] Error: Response from SAMPA not as expected
LNK_STS [31:0] 0x06 R 0x00 [31:0] Ethernet link status *
EVT_CFG [31:0] 0x07 RW 0x01 [1:0] Test signal output, see table 4.3
RW 0x00 [2] Enable SLVS testing
RW 0x00 [3] Enable continuous readout of shiftregister
RW 0x00 [31:3] Reserved *
EVT_CNT [31:0] 0x08 R 0x00 [31:0] Reserved *
EV_BL [31:0] 0x09 R 0x00 [31:0] Reserved *
SMP_STS1 [30:0] 0x0A R Status of signals to and from SAMPA (updated every clock cycle)
R [12:0] Test data output from SAMPA
R [16:13] Serial out [3:0]
R [18:17] Number of serial out
R [19] Enable ZSU
R [20] Enable BC2
R [21] Enable TCFU (deprecated)
R [22] Enable BC1
R [25:23] Select test output
R [26] Select ADC0 or test input
R [30:27] Chip address
SMP_STS2 [5:0] 0x0B R Status of signals to and from SAMPA cont.
R [0] Slow control to SAMPA
R [1] Slow control from SAMPA
R [2] Reset_n
R [3] Event trigger
R [4] Heartbeat trigger
R [5] Sync signal
SMP_CFG [13:0] 0x0C RW SAMPA static signals, see SAMPA spec document for further details
RW 0x02 [1:0] Number of serial out
RW 0x00 [2] Enable ZSU
RW 0x00 [3] Enable BC2
RW 0x01 [4] Enable TCFU
RW 0x01 [5] Enable BC1
RW 0x03 [8:6] Select test output
RW 0x01 [9] Select ADC0 or test input
RW 0x01 [13:10] Chip address
SLVS_ERR [15:0] 0x0D R 0x00 SLVS errors detected
RAD_ERR [31:0] 0x0E R Errors detected in shiftregister test
R 0x00 [15:0] Bit 0 errors
R 0x00 [31:16] Bit 1 errors

Commands for command and control unit.

Value Description
0x1 Reset FPGA and SAMPA
0x2 Reset SAMPA
0x3 Send event trigger
0x4 Send heartbeat trigger
0x5 Send sync signal
0x6 Run readout of shiftregister once (RAD)
0x7 Reset errors in shiftregister count (RAD_ERR)
0x8 Execute slow control command
0x9 Reset HPS

Test signals available for generation.

Value Description
0x0 Constant zeros
0x1 Sine wave, full wave, 512 samples pulse width
0x2 Saw wave, full wave, 512 samples pulse width
0x3 Triangle wave, full wave, 1024 samples pulse width

Data manager registers

The registers for the data manager module, located at address 0x0040 from the UART or 0xFF201000 from the HPS, is listed in table 4.4.

Register name Address Type Default Description
CNTRL [7:0] 0x00 RW 0x00 Control register
RW 0x00 [0] Enable acquisition
RW 0x00 [7:1] Reserved
PKT0 [31:0] 0x01 R 0x00 [31:0] Packets written to memory from channel 0
PKT1 [31:0] 0x02 R 0x00 [31:0] Packets written to memory from channel 1
PKT2 [31:0] 0x03 R 0x00 [31:0] Packets written to memory from channel 2
PKT3 [31:0] 0x04 R 0x00 [31:0] Packets written to memory from test-input/ADC
FIFO0 [8:0] 0x05 R 0x00 [8:0] Number of 64 bit words in FIFO 0
FIFO1 [8:0] 0x05 R 0x00 [8:0] Number of 64 bit words in FIFO 1
FIFO2 [8:0] 0x05 R 0x00 [8:0] Number of 64 bit words in FIFO 2
FIFO3 [8:0] 0x05 R 0x00 [8:0] Number of 64 bit words in FIFO 3